SKU: Conventional Type Heat Detector
Conventional Type Heat Detector Eco Series
Product Features: Dual Fire LED Indication. Thermistor Technology is used Current Output Stylish Look Compatible with all Fire Panel Low Standby Current
Product Description: Conventional 4 wire Heat detector IGNIS is a thermal heat detector that uses a static heat element of 57 °C. It is designed to respond when the convicted thermal energy of a fire increases the temperature of a heat sensitive element. The thermal mass and conductivity of the element regulate the rate flow of heat into the element. Heat detector operate when the heat sensitive eutectic alloy reaches the eutectic point changing state from a solid to a liquid. Thermal lag delays the accumulation of heat at the sensitive element so that a fixed-temperature device will reach its operating temperature sometime after the surrounding air temperature exceeds that temperature.
Application: The IGNIS Heat detector is suitable in general applications to help in the reduction of property damage. USPs:
● RED LED status indication in case of fire.
● Respond well to Heat Detection.
● Unaffected by wind or atmospheric pressure.
● Light weight.
● Elegant Design.
● Easy Installation.
The range of bases allows adapting the entire line of IGNIS detectors to the different installation needs. Its ample interior space makes mounting and electrical connection easier. Its special double-sided nickel-plated phosphor bronze terminals guarantee an optimal and reliable long-term contact with the detector.
Product Features: ● Thermal heat Detector model IGNIS. ● Available with low profile base and high base with four 20 mm inputs.●Independent head, bayonet system assembly and extraction lock. ● Nickel-plated phosphor bronze contacts, double-sided double-grip connection. ● SMT Design, High stability. ● Wide supply voltage range. ● Reverse polarity protection. ● 360˚ visible RED status LED and output for response indicator. ● ABS thermoplastic material and dust protective cover ● Size 100 x 36 (diameter x height)
Wiring Diagram: of conventional type Heat Detector:
Specification of Heat Detector: Truesafe
Detection method | Static Heat Element |
Fire Type | Heat |
Sensor type | Thermistor |
Reset time | 15 Sec Maximum |
Response time | 10 - 30 Sec |
Power supply | 12Vdc to 30Vdc |
Normal Current Consumption | 15uA at 24V at 25 ˚C (95uA at start-up) |
Alarm Current | 20 mA with R=470Ω at 24 V |
Operating temperature | -10 ˚C to 70 ˚C |
Storage temperature | -10 ˚C to 80 ˚C |
Humidity | 95% non-condensing |
Protection class | NA |
Cabinet material | ABS Thermoplastic |
Cable entry | NA |
Dimensions | 100 x 36 (diameter x height) |
Mounting | Ceiling mount |
Weight | 110 g |
Output | PFC output (Normally open or Normally closed dry contact) |
Accessories with Unit | 2 Screws (25*8 mm) Ravel Plug (25 mm) User Manual |